Egenskaber
Version | Surge voltage arrester, Low voltage, Accessories, Surge protection II |
Order No. | 1351190000 |
Type | VPU II 0 PV 1000V DC |
GTIN (EAN) | 4050118158847 |
Qty. | 1 Styk |
Depth | 64 mm |
Depth (inches) | 2,52 inch |
Height | 52 mm |
Height (inches) | 2,047 inch |
Width | 17,8 mm |
Width (inches) | 0,701 inch |
Net weight | 103 g |
Storage temperature | -40 °C...80 °C |
Operating temperature | -40 °C... |
RoHS Compliance Status | Compliant without exemption |
REACH SVHC | No SVHC above 0.1 wt% |
Colour | orange |
Design |
Installation housing; 1TE
Insta IP 20 |
Optical function display | green = OK; red = arrester is defective - replace |
Protection degree | IP20 |
Rail | TS 35 |
UL 94 flammability rating | V-0 |
Version | Surge protection II |
Pollution severity | 2 |
Surge voltage category | III |
Maximum continuous operating voltage DC UCPV mode +/-, -/PE, +/PE | 1.000 V |
Protection level Up (+/- , -/PE , +/PE) | ≤ 2.6 kV |
Protection level Up at IN (per module) | ≤ 2.8 kV |
PV system voltage, max. Ucpv | 1.000 V |
Requirements class | Type II |
Short-circuit curent ISCPV | 200 A |
Standards | EN 50539-11 |
Discharge current Imax (8/20µs) wire-PE | 25 kA |
Discharge current In (8/20µs) wire-PE | 12.5 kA |
Leakage current at Un | 30 µA |
Max. continuous voltage, Uc (DC) | 1000 V |
Number of poles | 1 |
Protection level Up at IN (L/N-PE) | ≤ 2.8 kV |
PV voltage, acc. to IEC 60364-7-712 | ≤ 1000 V |
Rated voltage (DC) | 1000 V |
Response time | ≤ 25 ns |
Standards | EN 50539-11 |
Voltage type | DC |
Type of connection | pluggable |
Voltage type | DC |
Number of poles | 1 |
Protection degree | IP20 |
Colour | orange |
Approval/Certificate/Document of Conformity | [EU_Konformitätserklärung / EU_Declaration_of_Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_86295) |
Eplan Data Portal | [Eplan data](https://dataportal.eplan.com/part-details/WEI.1351190000) |
User Documentation | [Beipackzettel / Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_35333) |
Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
ETIM 6.0 | EC000941 |
ETIM 7.0 | EC000941 |
ETIM 8.0 | EC000941 |
ETIM 9.0 | EC000941 |
ECLASS 9.0 | 27-13-08-05 |
ECLASS 9.1 | 27-13-08-05 |
ECLASS 10.0 | 27-13-08-05 |
ECLASS 11.0 | 27-13-08-05 |
ECLASS 12.0 | 27-17-90-90 |
ECLASS 13.0 | 27-17-90-90 |
ECLASS 14.0 | 27-17-90-90 |
Long specification | Spare arrestor consisting of V0 material for surge voltage arrestor VPU II 1000 VDC series The pluggable high-performance varistors can be exchanged by trained personnel following a failure. Rated voltage: 1000 VDC for PV systems Type: Weidmüller VPU II 0 PV 1000 VDC Order No.: 1351190000 |
Short specification | Spare arrester for surge voltage arrester VPU II 1000 V DC series The pluggable high-performance varistors can be swapped by trained personnel following a failure. Rated voltage: 1000 V DC for PV systems Type: Weidmüller VPU II 0 PV 1000 V DC Order no.: 1351190000 |
Approvals | ![CE](/picture/CE.gif) |
ROHS | Conform |