ACT20M-CI-2CO-S Item No. 1175990000
Please note that any possible discounts or additional costs are not yet applied here. The definitive payment amounts will be shown in the cart.





Properties
Version | Signal duplicator/isolator, Input : 0(4)-20 mA, Output : 2 x 0(4) - 20 mA |
Order No. | 1175990000 |
Type | ACT20M-CI-2CO-S |
GTIN (EAN) | 4032248969982 |
Qty. | 1 ST |
Depth | 114.3 mm |
Depth (inches) | 4.499991 inch |
Height | 112.5 mm |
Height (inches) | 4.429125 inch |
Net weight | 83.6 g |
Width | 6.1 mm |
Width (inches) | 0.240157 inch |
Storage temperature | -40 °C...85 °C |
Operating temperature | -25 °C...70 °C |
Humidity | 95 %, no condensation |
MTBF | 219 Years |
REACH SVHC | Lead 7439-92-1 |
Input | 0(4)-20 mA |
Input current |
0...20 mA
4…20mA |
Input resistance, current | 70 Ω |
Number of inputs | 1 |
Sensor |
Current source
Sensor with own supply 4-wire sensor |
Voltage drop, current input | < 1.5 V |
Cut-off frequency (-3 dB) | 100 Hz |
Load impedance current | @ max 23mA |
load impedance voltage | ≥ 10 kΩ |
Number of outputs | 2 |
Output | 2 x 0(4) - 20 mA |
Output current |
0...20 mA
4...20 mA |
Accuracy | < 0.05 % of measuring range |
Configuration | none |
Galvanic isolation | 3-way isolator |
Power consumption, max. | 0.75 W |
Power consumption, typ. | 0.53 W |
Rail | TS 35 |
Step response time | ≤ 7 ms |
Temperature coefficient | ≤ 0.01 % / °C |
Type of connection | Screw connection |
Voltage supply | 24 V DC ± 30 % |
EMC standards |
IEC 61326-1
NE 21 |
Galvanic isolation | 3-way isolator |
Insulation voltage | 2.5 kVeff /1 min. |
Pollution severity | 2 |
Rated voltage | 300 Veff |
Surge voltage category | II |
Marking | II 3 G Ex nA IIC T4 Gc |
Product information |
The non-adjustable DC isolating amplifier ACT20M-CI-CO-S isolates analogue standard current signals. An analogue input current signal is linearly converted to an analogue output current signal and is galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring or the Weidmüller rail bus.
The non-adjustable DC isolation amplifier ACT20M CI-2CO-S offers the same functionality, but has 2 galvanically isolated outputs (4-way isolation). |
Approval/Certificate/Document of Conformity |
[DNV-GL certificate](http://download.weidmueller.com/asset/download/file/86299)
[FM certificate](http://download.weidmueller.com/asset/download/file/102445) [IECEXx certificate](http://download.weidmueller.com/asset/download/file/102446) [ATEX certificate](http://download.weidmueller.com/asset/download/file/102447) [Declaration of Conformity](http://download.weidmueller.com/asset/download/file/35386) |
Brochure/Catalogue | [CAT 4.1 ELECTR 16/17 EN](http://download.weidmueller.com/asset/download/file/35322) |
Engineering Data | [STEP](http://download.weidmueller.com/asset/download/file/52202) |
Engineering Data | [EPLAN, WSCAD, Zuken E3.S](LINK/CAE_EN.html) |
CADENAS eCATALOG | [Cax data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=1175990000) |
User Documentation | [Instruction sheet](http://download.weidmueller.com/asset/download/file/35877) |
ETIM 6.0 | EC002653 |
ETIM 7.0 | EC002653 |
eClass 9.0 | 27-21-01-20 |
eClass 9.1 | 27-21-01-20 |
eClass 10.0 | 27-21-01-20 |
eClass 11.0 | 27210120 |
Long specification |
Standard signal splitter Isolation EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each other Type ACT20M-CI-2CO-S |
Short specification |
Standard signal splitter |
Approvals |         |
ROHS | Conform |
UL File Number Search | [E337701](LINK/UL_search.html) |