Egenskaber
Version | TERMSERIES, Relay with positively driven contacts, Number of contacts: 2, CO contacts forcibily guided (EN 61810-3 type B) AgNi, Rated control voltage: 24 V DC, Continuous current: 6 A, Plug-in connection, Test button available: No |
Order No. | 2723360000 |
Type | RCH424024FG |
GTIN (EAN) | 4050118786071 |
Qty. | 20 Styk |
Depth | 25,5 mm |
Depth (inches) | 1,004 inch |
Height | 29 mm |
Height (inches) | 1,142 inch |
Width | 12,6 mm |
Width (inches) | 0,496 inch |
Net weight | 19,5 g |
Storage temperature | -25 °C...70 °C |
Operating temperature | -25 °C...70 °C |
Humidity | 5...85 %, no condensation |
RoHS Compliance Status | Compliant without exemption |
REACH SVHC | No SVHC above 0.1 wt% |
Certificate No. (cURus) | E522350 |
Rated control voltage | 24 V DC |
Rated current DC | 29.2 mA |
Power rating |
585 mVA
565 mW |
Coil resistance | 823 Ω ± 10 % |
Status indicator | No |
Rated switching voltage | 250 V AC |
Continuous current | 6 A |
Max. switching frequency at rated load | 0,1 Hz |
Max. switching voltage, AC | 250 V |
Max. switching voltage, DC | 250 V |
Min. switching power | 10 mA @ 5 V |
AC switching capacity (resistive), max. | 1500 VA |
DC switching capacity (resistive), max. | 144 W @ 24 V |
Switch-on delay | ≤ 30 ms |
Switch-off delay | <20 ms |
Contact type | 2 CO contacts forcibily guided (EN 61810-3 type B) (AgNi) |
Mechanical service life | 10 x 106 switching cycles |
Rail | TS 35 |
Test button available | No |
Mechanical switch position indicator | No |
Colour | Transparent |
Rated voltage | 300 V |
Pollution severity | 2 |
Surge voltage category | III |
Clearance and creepage distances for control side - load side | ≥ 8 mm |
Dielectric strength for control side - load side | 4 kVeff / 1 Min. |
Type of isolation at input and output | reinforced insulation |
Dielectric strength of neighbouring contacts | 3 KVeff / 1 Min. |
Type of isolation at neighbouring contacts | reinforced insulation |
Dielectric strength of open contact | 1.5 kVeff /1 min. |
Impulse withstand voltage at neighbouring contacts | 6 kV (1.2/50 µs) |
Protection degree | IP20 |
Standards | EN 61810-3 |
Certificate No. (cURus) | E522350 |
Wire connection method | Plug-in connection |
Engineering Data | [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_103957) |
CADENAS eCATALOG | [CAX data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=2723360000) |
User Documentation | [FL_TERMSERIES_RCHFG_LOAD_GUIDE](https://mdcop.weidmueller.com/mediadelivery/asset/900_306016) |
Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
ETIM 6.0 | EC001437 |
ETIM 7.0 | EC001437 |
ETIM 8.0 | EC001437 |
ETIM 9.0 | EC001437 |
ECLASS 9.0 | 27-37-16-01 |
ECLASS 9.1 | 27-37-16-01 |
ECLASS 10.0 | 27-37-16-01 |
ECLASS 11.0 | 27-37-16-01 |
ECLASS 12.0 | 27-37-16-01 |
ECLASS 13.0 | 27-37-16-01 |
ECLASS 14.0 | 27-37-16-01 |
Approvals | ![CURUS](/picture/CURUS.gif) ![TUEV](/picture/TUEV.gif) |
ROHS | Conform |
UL File Number Search | [UL Website](LINK/UL_search.html) |
Certificate No. (cURus) | E522350 |