Version | Bolt-type screw terminals, Feed-through terminal, Rated cross-section: 120 mm², Threaded stud connection |
Order No. | 1861640000 |
Type | WF 10-8/2BZ GR |
GTIN (EAN) | 4032248497089 |
Qty. | 20 items |
Depth | 63,5 mm |
Depth (inches) | 2,5 inch |
Height | 67 mm |
Height (inches) | 2,638 inch |
Width | 32 mm |
Width (inches) | 1,26 inch |
Net weight | 0,111 g |
Storage temperature | -25 °C...55 °C |
Ambient temperature | -5 °C…40 °C |
Continuous operating temp., min. | −50 °C |
Continuous operating temp., max. | 120 °C |
RoHS Compliance Status | Compliant without exemption |
REACH SVHC | No SVHC above 0.1 wt% |
Material | Wemid |
Colour | grey |
UL 94 flammability rating | V-0 |
End cover plate required | No |
Number of potentials | 1 |
Number of levels | 1 |
Number of clamping points per level | 2 |
Levels cross-connected internally | No |
Rail | TS 35 |
N-function | No |
PE function | No |
PEN function | No |
Explosion-tested version | Yes |
Snap-on | Yes |
Type of mounting | Snap-on |
Clamping range, max. | 120 mm² |
Clamping range, min. | 6 mm² |
Connection cross-section, stranded, max. | 120 mm² |
Connection cross-section, stranded, min. | 6 mm² |
Connection direction | on side |
Number of connections | 2 |
Stud size for spade connection | M 10 |
Type of connection | Threaded stud connection |
Wire connection cross section AWG, max. | kcmil 250 |
Wire connection cross section AWG, min. | AWG 8 |
Wire connection cross section, finely stranded, max. | 120 mm² |
Wire connection cross section, finely stranded, min. | 6 mm² |
Wire connection cross-section, solid core, max. | 120 mm² |
Wire connection cross-section, solid core, min. | 6 mm² |
Certificate No. (CSA) | 200039-1244019 |
Current size C (CSA) | 325 A |
Voltage size C (CSA) | 1000 V |
Wire cross section max. (CSA) | 0000 AWG |
Wire cross section min. (CSA) | 00 AWG |
Rail | TS 35 |
Standards | IEC 60947-7-1 |
Wire connection cross section AWG, max. | kcmil 250 |
Wire connection cross section AWG, min. | AWG 8 |
Rated cross-section | 120 mm² |
Rated voltage | 1 000 V |
Rated DC voltage | 1 000 V |
Rated current | 269 A |
Current at maximum wires | 269 A |
Standards | IEC 60947-7-1 |
Volume resistance according to IEC 60947-7-x | 0,12 mΩ |
Power loss in accordance with IEC 60947-7-x | 8,61 W |
Pollution severity | 3 |
Surge voltage category | III |
Certificate No. (cURus) | E60693 |
Conductor size Factory wiring max. (cURus) | 0000 AWG |
Current size C (cURus) | 325 A |
Voltage size C (cURus) | 1000 V |
Approval/Certificate/Document of Conformity | |
Engineering Data | |
CADENAS eCATALOG | |
User Documentation | |
Catalogues |
ETIM 6.0 | EC000897 |
ETIM 7.0 | EC000897 |
ETIM 8.0 | EC000897 |
ETIM 9.0 | EC000897 |
ETIM 10.0 | EC000897 |
ECLASS 9.0 | 27-14-11-20 |
ECLASS 9.1 | 27-14-11-20 |
ECLASS 10.0 | 27-14-11-20 |
ECLASS 11.0 | 27-14-11-20 |
ECLASS 12.0 | 27-14-11-20 |
ECLASS 13.0 | 27-25-01-01 |
ECLASS 14.0 | 27-25-01-01 |
ECLASS 15.0 | 27-25-01-01 |
Approvals | ![]() ![]() ![]() ![]() |
ROHS | Conform |
UL File Number Search | |
Certificate No. (cURus) | E60693 |