Eigenschappen
Version | Limit value monitoring, Input: 3-phase voltage, Relay output |
Order No. | 7760054361 |
Type | ACT20P-VMR-3PH-ILP-H-P |
GTIN (EAN) | 4050118559750 |
Qty. | 1 items |
Depth | 114,3 mm |
Depth (inches) | 4,5 inch |
Height | 117 mm |
Height (inches) | 4,606 inch |
Width | 22,5 mm |
Width (inches) | 0,886 inch |
Net weight | 140 g |
Storage temperature | -40 °C...85 °C |
Operating temperature | -20 °C...65 °C |
Humidity at operating temperature | 0...95 % (no condensation) |
Humidity | 5...85 % rel. humidity, no condensation |
SIL in compliance with IEC 61508 | None |
RoHS Compliance Status | Compliant with exemption |
RoHS Exemption (if applicable/known) | 7a, 7cI |
REACH SVHC | Lead 7439-92-1 |
SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
Input resistance, voltage | ≥1,8MΩ |
Input voltage | 180…500 VAC |
Number of inputs | 1 |
Type |
3-phase or 3-phase plus zero conductor
AC voltage |
Number of outputs | 2 |
Alarm function |
Top and bottom limit values, window range
Holding function can be activated Phase error Phase sequence Asymmetry Alarm delay: 0…10 s |
Hysteresis | 5 % @ Phase asymmetry |
Max. switching voltage, AC | 250 V |
Max. switching voltage, DC | 30 V |
Number of digital outputs | 2 |
Rated switching current | 5 A |
Switch-on delay |
0…10 s
configurable |
Switching thresholds |
Adjustable
MIN = 50…100 % x URated input voltage (undervoltage alarm) MAX = 70…120 % x URated input voltage (overvoltage alarm) |
Type |
2 x 1 - or 1 x 2 changeover contact relay
Relay polarity can be inverted |
Accuracy | 3 % *Urated voltage |
Configuration | DIP switch and potentiometer |
Galvanic isolation |
2-way isolator
between input/output yes between input ⁄ output ⁄ supply |
Long-term drift | 0.1 % / 10.000 h |
Power consumption |
≤ 3VA
<2 W |
Protection degree | IP20 |
Rail | TS 35 |
Repeat accuracy | 2 % *Urated voltage |
Step response time | ≤ 100 ms |
Temperature coefficient | 350 ppm/K |
Voltage supply | supplied from voltage measurement inputs |
EMC standards | EN 61326-1 |
Galvanic isolation |
2-way isolator
between input/output yes between input ⁄ output ⁄ supply |
Impulse withstand voltage |
6 kV (input - output)
4 kV (output 1- output 2) 1.2/50 µs |
Insulation voltage | 2.5 kV (input / output) |
Pollution severity | 2 |
Rated voltage |
600 VAC (input - output)
300 VAC (output 1 - output 2) |
Surge voltage category | III |
Test voltage | 0,5 kV |
Type of connection | PUSH IN |
Tightening torque, min. | 0,4 Nm |
Tightening torque, max. | 0,6 Nm |
Clamping range, rated connection | 2,5 mm² |
Clamping range, min. | 0,5 mm² |
Clamping range, max. | 2,5 mm² |
Wire connection cross section AWG, min. | AWG 26 |
Wire connection cross section AWG, max. | AWG 14 |
Approval/Certificate/Document of Conformity | [Declaration of Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_35810) |
Engineering Data | [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_178168) |
CADENAS eCATALOG | [CAX data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=7760054361) |
Software | [DIP switch configuration tool](https://mdcop.weidmueller.com/mediadelivery/asset/900_35389) |
User Documentation | [Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_212944) |
Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
ETIM 6.0 | EC002654 |
ETIM 7.0 | EC002654 |
ETIM 8.0 | EC002654 |
ETIM 9.0 | EC002654 |
ECLASS 9.0 | 27-21-01-22 |
ECLASS 9.1 | 27-21-01-22 |
ECLASS 10.0 | 27-21-01-22 |
ECLASS 11.0 | 27-21-01-22 |
ECLASS 12.0 | 27-21-01-22 |
ECLASS 13.0 | 27-21-01-22 |
ECLASS 14.0 | 27-21-01-22 |
Approvals | ![CE](/picture/CE.gif) ![CURUS](/picture/CURUS.gif) |
ROHS | Conform |
UL File Number Search | [UL Website](LINK/UL_search.html) |
Certificate No. (cURus) | E469563 |