Ominaisuudet
Version | Frequency signal converter, exclusive of rail bus supply, Input : Frequency, Output : 0(4)-20 mA, 0(2)-10 V |
Order No. | 2825130000 |
Type | ACT20M-FRQ-AO-X-S |
GTIN (EAN) | 4064675360940 |
Qty. | 1 items |
Depth | 114,3 mm |
Depth (inches) | 4,5 inch |
Height | 112,5 mm |
Height (inches) | 4,429 inch |
Width | 6,1 mm |
Width (inches) | 0,24 inch |
Net weight | 999 g |
Storage temperature | -40 °C...85 °C |
Operating temperature | -25 °C...60 °C |
Humidity | 40 °C / 93 % rel. humidity, no condensation |
REACH SVHC | Lead 7439-92-1 |
SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
Input frequency | 0…100kHz |
Number of inputs | 1 |
Sensor |
NAMUR sensor, according to EN60947-5-6
NPN / PNP transistor (trig-level low: ≤4 V high: ≥7 V ) TTL (trig-level low: ≤0.8 V high: ≥2.0 V) Tacho (trig-level low: ≤-50 mV high: ≥+50 mV) Special current (trig-level: user-defined) Special voltage (trig-level: user-defined) S0 (trig-level low: ≤2.2 mA high: ≥9.0 mA ) |
Sensor supply | 5…17 V |
Load impedance current | ≤ 600 Ω |
load impedance voltage | ≥ 10 kΩ |
Number of outputs | 1 |
Output current |
0...20 mA
4...20 mA in case of sensor error downscale (3,5 mA) upscale (23 mA) |
Output signal limit | <28 mA |
Output voltage, note |
0(2)...10 V
0(1)...5 V 0(0,2)…1 V |
Type |
active
connected control must be passive |
Accuracy | Basic accuracy: 0.0002 Hz |
Configuration |
DIP switch
With FDT/DTM software |
Galvanic isolation | 3-way isolator |
Power consumption, max. | 1,2 W |
Power consumption, typ. | 0,65 W |
Rail | TS 35 |
Step response time |
≤ 30 ms
(0…90% / 100…10% of input level) |
Voltage supply | 24 V DC ± 30 % |
EMC standards |
IEC 61326-1
NE 21 |
Galvanic isolation | 3-way isolator |
Insulation voltage | 2.5 kVeff /1 min. |
Pollution severity | 2 |
Rated voltage | 300 Veff |
Surge voltage category | II |
Type of connection | Screw connection |
Tightening torque, min. | 0,4 Nm |
Tightening torque, max. | 0,6 Nm |
Clamping range, rated connection | 2,5 mm² |
Clamping range, min. | 0,5 mm² |
Clamping range, max. | 2,5 mm² |
Wire connection cross section AWG, min. | AWG 30 |
Wire connection cross section AWG, max. | AWG 14 |
EMC standards |
IEC 61326-1
NE 21 |
Product information | The universal frequency measuring transducer, which can be configured via software, disconnects and converts input signals (frequency, Namur, NPN, PNP, speedometer, TTL and S0) into an active analogue standard output signal. The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring. The model ACT20M-FRQ-AO-S can be supplied via the Weidmüller DIN rail bus |
Approval/Certificate/Document of Conformity | [Declaration of Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_307397) |
Engineering Data | [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_305589) |
Software |
[WI-Manager, DTM-Library for online installation](https://mdcop.weidmueller.com/mediadelivery/asset/900_35364)
[Release notes for Weidmueller FDT-DTM Software version](https://mdcop.weidmueller.com/mediadelivery/asset/900_248446) |
User Documentation | [Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_307393) |
Catalogues | [Catalogues in PDF-format](LINK/Catalog.html) |
ETIM 6.0 | EC002918 |
ETIM 7.0 | EC002918 |
ETIM 8.0 | EC002918 |
ETIM 9.0 | EC002918 |
ECLASS 9.0 | 27-21-01-28 |
ECLASS 9.1 | 27-21-01-28 |
ECLASS 10.0 | 27-21-01-28 |
ECLASS 11.0 | 27-21-01-28 |
ECLASS 12.0 | 27-21-01-28 |
ECLASS 13.0 | 27-21-01-28 |
Lisävarusteet
-
Tuotteen tunnus:1877680000VPE:320 items
MultiFit, Terminal marker, 5 x 7.5 mm, Pitch in mm (P): 7.50 Adels RKW, Phoenix, white
-
MarkersTerminal markersMultiCardMultiFitMF 5/...Blank
Analogue Signal ConditioningAccessoriesConfiguration interfaces