Version | Photovoltaics, Combiner Box, PV Next, 1100 V, 2 MPP's, 3 Inputs / 3 Outputs per MPP, Surge protection I / II, Switch disconnector, Cable gland |
Order No. | 2890600000 |
Type | PVN DC 3I 3O 2MPP SW SPD1R CG 11 |
GTIN (EAN) | 4064675878445 |
Qty. | 1 items |
Depth | 172 mm |
Depth (inches) | 6,772 inch |
Height | 235 mm |
Height (inches) | 9,252 inch |
Width | 400 mm |
Width (inches) | 15,748 inch |
Net weight | 4.210 g |
Ambient temperature | -40 °C...+50 °C |
Humidity | 5...95 %, no condensation |
RoHS Compliance Status | Compliant |
REACH SVHC | Lead 7439-92-1 |
SCIP | bdab5698-6a20-4370-8e28-8810d882d01a |
Time interval | 5 years |
Current per Maximum Power Point, max. | 50 A |
Rated DC voltage | 1.100 V |
Rated short-term current resistance |
|
Connection type string | Internal terminal (with cable gland feed-through) |
Enclosure attachment | Via mounting foots |
Impact resistance |
IK08 in accordance with IEC 62208
IK10 in accordance with IEC 62262 |
Insulating material |
Polyester glass-fibre reinforced, Polycarbonate
Polycarbonate |
Protection class | II |
Type of mounting | Wall mounting |
Installation location | Protected outdoor area (Land and Sea) |
Protection degree | IP65 |
Standards | EN 61643-31 |
Amount of maximum power points (MPP) | 2 |
DC Input + & - |
|
Functional earth connector |
|
Fuse type | Neither fuse cartridge nor holder |
Fuses | No |
Max. number of DC inputs | per Maximum Power Point 3 inputs connected in parallel |
Number of conduit inlets | 2 |
Number of string inputs per MPP | ≤ 3 |
Surge protection auxiliary contact |
|
Number of inputs | 3 |
DC Output + & - |
|
Max. number of DC outputs | per Maximum Power Point 3 outputs connected in parallel |
Discharge current In (8/20 µs) | 20 kA |
Discharge current, max. (8/20 µs) | 40 kA |
Lightning test current Iimp (10/350 µs) | 6.25 kA |
Maximum continuous operating voltage DC UCPV mode +/-, -/PE, +/PE | 1.100 V |
Protection level Up (+/- , -/PE , +/PE) | ≤ 3.8 kV |
Protection level Up (+/-) | ≤ 3.8 kV |
Protection level Up (+/PE) | ≤ 3.8 kV |
Protection level Up (-/PE) | ≤ 3.8 kV |
PV system voltage, max. Ucpv | 1.100 V |
Requirements class | Type I/II |
Short-circuit curent ISCPV | 11.000 A |
Standards | EN 61643-31 |
Standby power consumption PC | <0.2 W |
Surge protection DC side | 1000 V type I + II |
Total discharge current Itotal ( 8/20µs) | 50 kA |
Total discharge current Itotal (10/350µs) | 12,5 kA |
Motor drive available | No |
Number of breaking operation cycles at rated current | 300 |
Number of operating cycles | 10000 |
Rated impulse withstand voltage | 8 kV |
Rated short-circuit making current | 1,4 A |
Switch disconnector execution | switch in cover |
Switching disconnector capacity |
DC-PV1
IEC 60947-3 |
Product information |
The SCIP number was assigned due to a lead content of more than 0.1 % of the net weight. Safe use instruction according to ECHA: The identification of the hazardous substance is sufficient to allow safe use of the article throughout its life cycle, including the service life, disassembly and waste/recycling phase |
Approval/Certificate/Document of Conformity | |
Engineering Data | |
Eplan Data Portal | |
CADENAS eCATALOG | |
WSCAD Universe | |
Technical Documentation | |
User Documentation | |
White paper | Fact Sheet DE PV CB Wie man Gebäude gegen Blitzeinschläge schütztFact Sheet DE PV Wie man die Lebensdauer eines GAK verlängertFact-Sheet EN PV CB Load break switchFact Sheet EN CB Combining PV stringsFact Sheet EN PV Combiner Box earthingFact Sheet DE PV Combiner Box ErdungFact Sheet DE PV CB Wann Sicherungen zu installieren sindFact Sheet DE CB PV NEXTFact Sheet EN PV CB When DC fuses are mandatory to installFact Sheet EN CB PV NEXTFact Sheet EN PV How to protect buildings against lightning strikesFact Sheet EN PV How to extend the life time of a Combiner BoxFact Sheet DE PV CB LastentrennschalterFact Sheet DE CB PV Strings kombinieren |
Catalogues |
ETIM 6.0 | EC002928 |
ETIM 7.0 | EC002928 |
ETIM 8.0 | EC003857 |
ETIM 9.0 | EC003857 |
ECLASS 9.0 | 22-57-92-03 |
ECLASS 9.1 | 22-57-02-90 |
ECLASS 10.0 | 22-57-02-90 |
ECLASS 11.0 | 22-57-02-92 |
ECLASS 12.0 | 22-57-02-92 |
ECLASS 13.0 | 22-57-02-92 |
ECLASS 14.0 | 22-57-02-92 |
Long specification |
Combiner box for inverters with 2 MPP tracker, suitable for protecting the DC side of a photovoltaic system according to EN 51543-32. MPP1: Max. string voltage Uoc: 1100V Approval according to low voltage switchgear and controlgear IEC 61439-1:2011 and EN 61439-2:2011 |
Approvals | ![]() |
ROHS | Conform |
-
Product ID:2659350000VPE:100 items
Cable ties, 4.5 x 290 mm, Polyamide 66, 220 N
-
Product ID:9536040000VPE:1 items
FPC (polycarbonate empty enclosure), Mounting foot, Fixing lugs, Height: 40 mm, Width: 19 mm, Depth: 35.5 mm, Material: Polyamide, Light Grey
-
Product ID:3077650000VPE:1 items
Photovoltaics, Blind plug, Accessories, Blind plug, 50 pieces
-
Product ID:2877860000VPE:1 items
Photovoltaics, Y-Connector Cable, 1x WM4 C Male, 2x MC4 Female, 6mm², 1500 V
-
Product ID:2877850000VPE:1 items
Photovoltaics, Y-Connector Cable, 1x WM4 C Female, 2x MC4 Male, 6mm², 1500 V
-
Product ID:2530600000VPE:9 items
Surge voltage arrester, Low voltage, Accessories, Surge protection I / II, Spare arrester
-
Product ID:2534300000VPE:9 items
Surge voltage arrester, Low voltage, Surge protection I / II, Spare arrester