ACT20M-CI-CO-ILP-S   Item No. 1176070000

Signal converter/insulator, Input current loop feed, 1-channel, Input : 4-20 mA, Output : 4-20 mA

Please note that any possible discounts or additional costs are not yet applied here. The definitive payment amounts will be shown in the cart.

ACT20M-CI-CO-ILP-S ACT20M-CI-CO-ILP-S ACT20M-CI-CO-ILP-S ACT20M-CI-CO-ILP-S ACT20M-CI-CO-ILP-S

Properties

Type ACT20M-CI-CO-ILP-S  
Order No. 1176070000  
Version Signal converter/insulator, Input current loop feed, 1-channel, Input : 4-20 mA, Output : 4-20 mA  
GTIN (EAN) 4032248970148  
Qty. 1 ST  
Width 6.1 mm  
Width (inches) 0.240157 inch  
Height 112.5 mm  
Height (inches) 4.429125 inch  
Depth 114.3 mm  
Depth (inches) 4.499991 inch  
Net weight 80 g  
Humidity 40 °C / 93 % rel. humidity, no condensation  
Operating temperature, max. 70 °C  
Operating temperature, min. -25 °C  
Storage temperature, max. 85 °C  
Storage temperature, min. -40 °C  
Operating temperature -25 °C...70 °C  
Ambient temperature -25 °C...+70 °C  
Storage temperature -40 °C...85 °C  
MTBF 699 Years  
REACH SVHC Lead 7439-92-1  
Number of inputs 1  
Sensor Current source  
Input current 0...20 mA  
4…20mA  
Voltage drop, current input 1.25 V + 0.015 Vout @25°C  
Input frequency 100 Hz  
Number of outputs 1  
Output current 0...20 mA  
4...20 mA  
Cut-off frequency (-3 dB) 100 Hz  
load impedance current ≤600 Ω  
Accuracy < 0.1 % of measuring range  
Configuration none  
Galvanic isolation 2-way isolator  
Power consumption 30 mW per channel  
Rail TS 35  
Step response time ≤ 5 ms  
Temperature coefficient ≤ 0.01 % / °C  
Voltage supply Loop powered, via 4…20 mA input  
EMC standards IEC 61326-1  
NE 21  
Galvanic isolation 2-way isolator  
Insulation voltage 2.5 kVeff /1 min.  
Pollution severity 2  
Rated voltage 300 Veff  
Standards IEC 61010-1  
Surge voltage category II  
Marking II 3 G Ex nA IIC T4 Gc  
Type of connection Screw connection  
Tightening torque, min. 0.4 Nm  
Tightening torque, max. 0.6 Nm  
Clamping range, rated connection 2.5 mm²  
Clamping range, min. 0.5 mm²  
Clamping range, max. 2.5 mm²  
Wire connection cross section AWG, min. AWG 30  
Wire connection cross section AWG, max. AWG 14  
Certificate No. (ATEX) KEMA10ATEX0183X  
Certificate No. (IECEX) IECEXKEM10.0090X  
Product information The ACT20M-CI-CO-ILP-S passive isolator isolates standard analogue current signals.An analogue input current signal is linearly converted to an analogue output current signal and is galvanically isolated. Power is supplied through the input measuring circuit (input loop-powered).  
Descriptive text technical data Power supply optionally over the DIN mounting rail CH20M  
Instructions for accessories DIN mounting rail, see Accessories  
Approval/Certificate/Document of Conformity [DNV-GL certificate](http://download.weidmueller.com/asset/download/file/86299)  
[Declaration of Conformity](http://download.weidmueller.com/asset/download/file/35386)  
Brochure/Catalogue [CAT 4.1 ELECTR 16/17 EN](http://download.weidmueller.com/asset/download/file/35322)  
Engineering Data [EPLAN, WSCAD, Zuken E3.S](LINK/CAE_EN.html)  
Engineering Data [STEP](http://download.weidmueller.com/asset/download/file/52196)  
User Documentation [Instruction sheet](http://download.weidmueller.com/asset/download/file/35876)  
Long specification

Standard signal passive isolator
1-channel passive isolator in 6.1 mm width input-loop powered,
for transmitting and isolating analogue DC current signals 0/4...20 mA.

Add-on housing for TS35 rail mounting
Dimensions: L/W/H 114.3/ 6.1/ 112.5 mm
Screw connection / Nominal cross-section 2.5 mm2
Protection degree: IP 20  


Input                          0/4...20 mA

Output                                              0/4...20 mA
Load resistance             < 600 Ohm
Transmission error               < 0,1 % v. E. 
Limit frequency 100 Hz
Auxiliary power                                     0/4...20 mA input current loop
Power loss approx. 0.9 W
Ambient
temperature range -25 °C...+70 °C

Isolation                                 EN 61010-1, 2-way isolation up to 2.5 kV AC/DC
Test voltage                               2.5 kV input against output against auxiliary power
Rated
voltage                                        
  300 V AC/DC at overvoltage category II and pollution degree 2
Approvals cULus, FM Div2, ATEX Zone2, DNV, GL




Type                                                             ACT20M-CI-CO-ILP-S

 
Short specification Standard signal passive isolator
1-channel signal passive isolator in 6.1 mm width with input current loop feed,
for transmitting and isolating analogue DC current signals from 0/4 to 20 mA
 
eClass 6.2 27-21-01-20  
eClass 7.1 27-21-01-20  
eClass 8.1 27-21-01-20  
eClass 9.0 27-21-01-20  
eClass 9.1 27-21-01-20  
ETIM 3.0 EC002479  
ETIM 4.0 EC002653  
ETIM 5.0 EC002653  
ETIM 6.0 EC002653  
Approvals ![CULUS](/picture/CULUS.gif) ![DETNORVER](/picture/DETNORVER.gif) ![DNVGL](/picture/DNVGL.gif) ![EAC](/picture/EAC.gif) ![FMEX](/picture/FMEX.gif) ![IECEXKEM](/picture/IECEXKEM.gif) ![KEMAATEX](/picture/KEMAATEX.gif)  
ROHS Conform  
UL File Number Search [E337701](LINK/UL_search.html)  

Accessories

  • Item No.
    1877680000