ACT20M-CI-CO-OLP-S   Item No. 1176040000

Signal converter/insulator, Output current loop powered, 1-channel, Input : 4-20 mA, Output : 4-20 mA

Properties

Version Signal converter/insulator, Output current loop powered, 1-channel, Input : 4-20 mA, Output : 4-20 mA  
Order No. 1176040000  
Type ACT20M-CI-CO-OLP-S  
GTIN (EAN) 4032248970155  
Qty. 1 ST  
Depth 114.3 mm  
Depth (inches) 4.499991 inch  
Height 112.5 mm  
Height (inches) 4.429125 inch  
Width 6.1 mm  
Width (inches) 0.240157 inch  
Net weight 80 g  
Storage temperature -40 °C...85 °C  
Operating temperature -25 °C...70 °C  
Humidity 40 °C / 93 % rel. humidity, no condensation  
REACH SVHC Lead 7439-92-1  
Input current 4…20mA  
Number of inputs 1  
Sensor 2-wire transmitter (without own power supply)  
Sensor supply 6…35 V (@ 20 mA)  
Voltage drop, current input Typical 2.5 V  
Cut-off frequency (-3 dB) 100 Hz  
Load impedance current ≤600 Ω (Kanal 1 +2)  
≤600 Ω (canale 1 + 2)  
≤600 Ω (channel 1 + 2)  
≤600 Ω (Kanal 1 +2)  
≤600 Ω (voie 1 + 2)  
≤ 600 Ω (1. + 2. csatorna)  
≤600 Ω (kanał 1 +2)  
≤600 Ω (canal 1 + 2)  
≤600 Ом (канал 1 +2)  
≤600 Ω (通道 1 +2)  
≤ 600 Ω (kanál 1 +2)  
@ max 23mA  
Number of outputs 1  
Output current 4...20 mA  
Supply voltage (output) 6…35 V  
Type passive  
connected control must be active  
Accuracy < 0.05 % of measuring range  
Configuration none  
Galvanic isolation 2-way isolator  
Power consumption, max. 0.5 W  
Rail TS 35  
Step response time ≤ 5 ms  
Temperature coefficient ≤±0.02 µA x (Δ °C x V supply) @ Tamb > 25 °C  
Type of connection Screw connection  
Voltage supply Output loop powered  
EMC standards IEC 61326-1  
NE 21  
Galvanic isolation 2-way isolator  
Insulation voltage 2.5 kVeff /1 min.  
Pollution severity 2  
Rated voltage 300 Veff  
Surge voltage category II  
Marking II 3 G Ex nA IIC T4 Gc  
Type of connection Screw connection  
Tightening torque, min. 0.4 Nm  
Tightening torque, max. 0.6 Nm  
Clamping range, rated connection 2.5 mm²  
Clamping range, min. 0.5 mm²  
Clamping range, max. 2.5 mm²  
Wire connection cross section AWG, min. AWG 30  
Wire connection cross section AWG, max. AWG 14  
EMC standards IEC 61326-1  
NE 21  
Standards IEC 61010-1  
Product information The passive isolator ACT20M-CI-CO-OLP-S isolates standard analogue current signals. An analogue input current signal is linearly converted into an analogue output current signal and is galvanically isolated. Power is supplied through the output measuring circuit (output loop-powered).  
Approval/Certificate/Document of Conformity [DNV-GL certificate](https://mdcop.weidmueller.com/mediadelivery/asset/900_86299)  
[FM certificate](https://mdcop.weidmueller.com/mediadelivery/asset/900_102445)  
[IECEXx certificate](https://mdcop.weidmueller.com/mediadelivery/asset/900_102446)  
[ATEX certificate](https://mdcop.weidmueller.com/mediadelivery/asset/900_102447)  
[Declaration of Conformity](https://mdcop.weidmueller.com/mediadelivery/asset/900_35386)  
Engineering Data [CAD data -- STEP](https://mdcop.weidmueller.com/mediadelivery/asset/900_52197)  
Engineering Data [EPLAN, WSCAD, Zuken E3.S](LINK/CAE_EN.html)  
CADENAS eCATALOG [Cax data](https://weidmueller-embedded.partcommunity.com?catalog=weidmueller_qs&part=1176040000)  
User Documentation [Instruction sheet](https://mdcop.weidmueller.com/mediadelivery/asset/900_35875)  
Catalogues [Catalogues in PDF-format](LINK/Catalog.html)  
ETIM 6.0 EC002653  
ETIM 7.0 EC002653  
ETIM 8.0 EC002653  
ECLASS 9.0 27-21-01-20  
ECLASS 9.1 27-21-01-20  
ECLASS 10.0 27-21-01-20  
ECLASS 11.0 27-21-01-20  
Long specification

Standard signal isolating amplifier
1-channel signal isolating amplifier in 6.1 mm width output-loop powered,
for transmitting and isolating analogue DC current signals 0/4...20 mA.

Add-on housing for TS35 rail mounting
Dimensions: L/W/H 114.3/ 6.1/ 112.5 mm
Screw connection / Nominal cross-section 2.5 mm2
Protection degree: IP 20  


Input                         0/4...20 mA

Output                                             0/4...20 mA
Load resistance             < 600 Ohm
Transmission error             < 0,1 % v. E. 
Limit frequency 100 Hz
Auxiliary power                                     0/4...20 mA output current loop
Power loss approx. 0.9 W
Ambient
temperature range -25 °C...+70 °C

Isolation                                EN 61010-1, 2-way isolation up to 2.5 kV AC/DC
Test voltage                               2.5 kV input against output against auxiliary power
Rated
voltage                                        
  300 V AC/DC at overvoltage category II and pollution degree 2
Approvals cULus, FM Div2, ATEX Zone2, DNV, GL




Type                                                             ACT20M-CI-CO-OLP-S

 
Short specification Standard signal isolating amplifier
1-channel signal isolating amplifier in 6.1 mm width with output current loop feed,
for transmitting and isolating analogue DC current signals from 0/4 to 20 mA.
 
Approvals ![CULUS](/picture/CULUS.gif) ![DETNORVER](/picture/DETNORVER.gif) ![EAC](/picture/EAC.gif) ![FMEX](/picture/FMEX.gif) ![IECEXKEM](/picture/IECEXKEM.gif) ![KEMAATEX](/picture/KEMAATEX.gif)  
ROHS Conform  
UL File Number Search [E337701](LINK/UL_search.html)  

Accessories

  • Item No.
    1877680000