ACT20M-UI-AO-S   Item No. 1176030000

Signal converter/insulator, Temperature converter, universal, 2-/3-/4- wire RTD, Thermocouple, Input : universal U, I, R,ϑ, Output : I / U

Please note that any possible discounts or additional costs are not yet applied here. The definitive payment amounts will be shown in the cart.

ACT20M-UI-AO-S ACT20M-UI-AO-S ACT20M-UI-AO-S ACT20M-UI-AO-S ACT20M-UI-AO-S

Properties

Type ACT20M-UI-AO-S  
Order No. 1176030000  
Version Signal converter/insulator, Temperature converter, universal, 2-/3-/4- wire RTD, Thermocouple, Input : universal U, I, R,ϑ, Output : I / U  
GTIN (EAN) 4032248970070  
Qty. 1 ST  
Width 6.1 mm  
Width (inches) 0.240157 inch  
Height 112.5 mm  
Height (inches) 4.429125 inch  
Depth 114.3 mm  
Depth (inches) 4.499991 inch  
Net weight 80 g  
Humidity 40 °C / 93 % rel. humidity, no condensation  
Operating temperature, max. 70 °C  
Operating temperature, min. -25 °C  
Storage temperature, max. 85 °C  
Storage temperature, min. -40 °C  
Operating temperature -25 °C...70 °C  
Ambient temperature -25 °C...+70 °C  
Storage temperature -40 °C...85 °C  
MTBF 176 Years  
REACH SVHC Lead 7439-92-1  
UL certificate [E337701.pdf](PDF/QUYX.E337701.pdf)  
Number of inputs 1  
Sensor Thermocouples: B / C / E / J / K / L / N / R / S / T / W3 / W5
- 200...+ 2300 °C depending on thermocouple  
RTD: PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000  
2-/3-/4-wire  
Sensor supply > 15 V DC at 20 mA  
Input voltage 0(2)…10 V  
0(1)…5 V  
0…1 V DC  
0,2…1 V DC  
Input resistance, voltage > 10 MΩ  
Input current 0...20 mA  
4…20mA  
Voltage drop, current input < 3 V  
Temperature input range PT100: -200°C…850 °C  
NI100: -60°C…+250 °C  
E: (-100…+1000 °C)  
J: (-100…+1200 °C)  
K: (-180…+1372 °C)  
L: (-200…+900 °C)  
N: (-180…+1300 °C)  
R: (-50…+1760 °C)  
S: (-50…+1760 °C)  
T: (-200…+400 °C)  
U: (-200…+600 °C)  
W3: (0…+2300 °C)  
W5: (0…+2300 °C)  
LR: (-200…+800 °C)  
Details under Downloads "Measuring range Table ACT20M-UI-AO"  
Resistance 0…10 kΩ  
Potentiometer 10…100 kΩ  
Number of outputs 1  
Output voltage, note 0(2)...10 V  
0(1)...5 V  
0(0,2)…1 V  
1…(0,2)0 V  
5…(1)0 V  
10…(2)0 V  
downscale (0 V)  
upscale (11 V)  
Output current 0...20 mA  
4...20 mA  
20…0 mA  
20…4 mA  
downscale (3,5 mA)  
upscale (23 mA)  
Cut-off frequency (-3 dB) 100 Hz  
cold junction compensation internal  
load impedance voltage ≥ 10 kΩ  
load impedance current @ max 28mA  
Accuracy < 0.1 % of measuring range  
Configuration With FDT/DTM software  
Galvanic isolation 3-way isolator  
Power consumption, max. 1.2 W  
Power consumption, typ. 0.84 W  
Rail TS 35  
Step response time 400 ms (10...90%) @ U/I  
Temperature coefficient ≤ 0.01 % / °C  
Voltage supply 24 V DC ± 30 %  
EMC standards IEC 61326-1  
NE 21  
Galvanic isolation 3-way isolator  
Insulation voltage 2.5 kVeff /1 min.  
Pollution severity 2  
Rated voltage 300 Veff  
Standards IEC 61010-1  
Surge voltage category II  
Marking II 3 G Ex nA IIC T4 Gc  
Type of connection Screw connection  
Tightening torque, min. 0.4 Nm  
Tightening torque, max. 0.6 Nm  
Clamping range, rated connection 2.5 mm²  
Clamping range, min. 0.5 mm²  
Clamping range, max. 2.5 mm²  
Wire connection cross section AWG, min. AWG 30  
Wire connection cross section AWG, max. AWG 14  
Certificate No. (ATEX) KEMA10ATEX0183X  
Certificate No. (IECEX) IECEXKEM10.0090X  
Product information The software configurable Universal Transmitter ACT20M-UI-AO-S separates and converts standard analogue signals. An analogue input signal (voltage, current, resistance, potentiometer, RTD, TC) is converted linear and galvanic isolated into an analogue output signal. The input may also operate as an active current loop (the loop current provided by the device). The power supply is galvanically isolated from input and output and happens via a direct wiring or the Weidmüller DIN Rail Bus (3-way isolation).  
Descriptive text technical data Power supply optionally over the DIN mounting rail CH20M  
Instructions for accessories CBX200 USB configuration adapter - 8978580000
DIN mounting rail, see Accessories  
Approval/Certificate/Document of Conformity [DNV-GL certificate](http://download.weidmueller.com/asset/download/file/86299)  
[Declaration of Conformity](http://download.weidmueller.com/asset/download/file/35386)  
Brochure/Catalogue [CAT 4.1 ELECTR 16/17 EN](http://download.weidmueller.com/asset/download/file/35322)  
Engineering Data [EPLAN, WSCAD, Zuken E3.S](LINK/CAE_EN.html)  
Engineering Data [STEP](http://download.weidmueller.com/asset/download/file/52200)  
Software [WI-Manager, DTM-Library for online installation V.1.2.0](http://download.weidmueller.com/asset/download/file/35364)  
User Documentation [Instruction sheet](http://download.weidmueller.com/asset/download/file/38120)  
[measuring range table](http://download.weidmueller.com/asset/download/file/49603)  
Long specification

Universal measurement isolating transformer
universal measurement isolating transformer in 6.1 mm width with external power and sensor power supply
to transmit and isolate analogue DC currents 0/4 to 20 mA / voltages 0/2 to 10 V,
2-/3-/-4- wire RTD, resistances, potentiometers and thermocouples according toIEC584.
The module can be programmed via software using standard FDT/DTM tools.

Add-on housing for TS35 DIN rail installation
Dimensions: L/W/H 114.3/ 6.1/ 112.5 mm
Screw connection / nominal cross-section 2.5 mm2
Protection degree: IP20 Input0/4...20 mA 0/2...10 V PT100, PT1000, Ni100, Ni1000
Resistance/ potentiometer 10 Ohm...10 kOhm Thermocouples type B, E, J, K, L, LR, N, R, S, T, U, W3, W5
Sensor supply > 15 VDC at 20 mA

Output 0/4...20 mA 0/2...10 VLoad resistance
10 kOhm/ voltageTransmission error
< 600 Ohm/ Strom/>Step response time
10...90 % Auxiliary power 24 VDC +/- 30 %Power loss approx. 1.2 WAmbient< 0,1 % v. E. (DC, RTD)
temperature range -25 °C...+70 °C



Isolation EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each other
Test voltage 2.5 kV input against output against auxiliary power
Rated
voltage 300 V AC/DC at overvoltage category II and pollution degree 2
Approvals cULus, FM Div2, ATEX Zone2, DNV, GL




Type ACT20M-UI-AO-S


 
Short specification Universal measurement isolating transformeruniversal measurement isolating transformer in 6.1 mm width with external power and sensor power supply for transmitting and isolating analogue DC currents 0/4 to 20 mA / voltages 0/2 to 10 V, 2-/3-/-4- wire RTD, resistances, potentiometers and thermocouples according to IEC584. The component can be programmed via software using standard FDT/DTM tools.


 
eClass 6.2 27-21-01-20  
eClass 7.1 27-21-01-20  
eClass 8.1 27-21-01-20  
eClass 9.0 27-21-01-20  
eClass 9.1 27-21-01-90  
ETIM 3.0 EC002479  
ETIM 4.0 EC002653  
ETIM 5.0 EC002653  
ETIM 6.0 EC002653  
Approvals ![CULUS](/picture/CULUS.gif) ![DETNORVER](/picture/DETNORVER.gif) ![DNVGL](/picture/DNVGL.gif) ![EAC](/picture/EAC.gif) ![FMEX](/picture/FMEX.gif) ![IECEXKEM](/picture/IECEXKEM.gif) ![KEMAATEX](/picture/KEMAATEX.gif)  
ROHS Conform  
UL File Number Search [E337701](LINK/UL_search.html)  

Accessories

  • Item No.
    8978580000
  • Item No.
    1877680000
  • Item No.
    1282490000
  • Item No.
    1335140000